Nelson Firestop - ES1399™ Elastomeric Sealant,10.3 OZ Tube,AA0870
|
MSRP: $23.50
$14.65
You Save: $8.85 (38 %)
Manufacturer: Nelson Fire Stop Products
Manufacturer Part No: AA0870
PHTS Number: NELAA0870
|
ES1399™ Elastomeric Sealant
Technical Data
Product Description
Nelson Firestop Elastomeric Sealant (ES1399™) is a cost effective, water based acrylic latex, endothermic, fire protective sealant. It is designed for applications of through firestop penetrations and in construction joints.
Application
ES1399™ sealant can be applied using a conventional small caulk gun, bulk loader or by trowel. ES1399™ is applicable for through firestop penetrations and for floor to wall, floor-to-floor and head of wall applications. It is flexible and is ideal for applications where joint expansion and contraction can occur. Apply the required depth of sealant beginning on the edge of the opening (use over various backing materials as required). Insure that the sealant makes complete contact with the inside surface of the opening and also the surface of the penetrating item(s). On joints, the surfaces should be clean and free of dust, dirt, oil, grease, loose material, rust or other substances. Apply the required thickness in the joint or over the insulation if required.
Availability
AA0870 – Non/Sag-10.3 oz Tube 18.5 in3 (304ml) 12/Ctn.
Approvals
Underwriters Laboratories Inc.Fill, Void or Cavity Material (XHHW)
City of New York, New York, Department of Buildings. MEA 125-04-M
Features
Up to 4-Hour ratings
Water-Based Acrylic Latex – Easy clean-up
Economical
Elastomeric (Flexible Cure)
Paintable
Water Resistant
Acoustically Tested – Reduces noise transmission
Physical Properties
Color……………….Red
Weight……………..10.75 lbs. per gallon
Consistency...……..Thixotropic
Application Temp…40°F (4°C) to 90°F (32°C)
STC Rating………………52
Test Compliance
ASTM E84
Flame spread……………..0
Smoke developed….……30
ASTM E90 Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements
ASTM E814 and UL1479 Test method for through stop fire penetrations.
ASTM E1399 Test method for cyclic movement and measuring min. and max. joint width.
ASTM E1966 and UL2079 Test method for fire resistance of building joint systems.
Storage & Handling
Nelson ES1399™ should be stored at temperatures between 40°F (4°C) and 90°F (32°C). Protect from freezing. Expected shelf life is one year from date of shipment.
|
|